Siri XMT-908 Pengawal Suhu Jenis Input Universal
dapatkan harga terkiniJenis bayaran: | T/T,Paypal |
Incoterm: | FOB,CFR,CIF,EXW |
Pesanan minimum: | 2 Piece/Pieces |
Pengangkutan: | Ocean,Land,Air,Express |
Port: | NINGBO,SHANGHAI, |
Jenis bayaran: | T/T,Paypal |
Incoterm: | FOB,CFR,CIF,EXW |
Pesanan minimum: | 2 Piece/Pieces |
Pengangkutan: | Ocean,Land,Air,Express |
Port: | NINGBO,SHANGHAI, |
Model No.: XMT-908
Jenama: CJ
Control Typel: Digita
Control Method: Electronic Type
Unit Jualan | : | Piece/Pieces |
Ⅰ 、 Spesifikasi Teknikal Utama
L Penyimpangan Pengukuran: ≤ ± 0.5%F ± S ± 1
L Penyimpangan Pencegahan Akhir: ≤ ± 2.0 ℃
l Kitaran pensampelan: 0.5s
l Kitaran kawalan: Output relay 2 ~ 120s, yang lain ialah 2s.
l Kapasiti hubungan output relay: AC250V/7A (beban rintangan) atau AC250V/0.3A (beban persepsi)
l Panduan Pulse yang boleh dikawal: Skop ≥3V, ≥40US lebar melebihi sifar atau mencetuskan nadi kenalan
l Memandu output isyarat relay pepejal: Memandu elektrik semasa ≥15mA, voltage ≥9V.
l PID berterusan: 0 ~ 10mA (beban 500 ± 200Ω), 4 ~ 20mA (beban 250 ± 100Ω),
atau 0 ~ 5V (beban ≥100kΩ), 1 ~ 5V (beban ≥100kΩ)
L Bekalan Kuasa: AC85V ~ 242V, 50/60Hz
l Keadaan kerja: Suhu 0 ~ 50.0 ℃, kelembapan relatif ≤85%RH, tanpa menghancurkan dan radiasi elektrik yang kuat.
Ⅱ 、 Kod Produk:
Xmt □ 9 □ 8 □
(1) ⑵ (3) (4) (5)
(1) dimensi muka meter
Kosong: 160mm × 80mm x 120mm lubang pemasangan: 152mm x 76mm
A: 96mm x 96mm x 110mm lubang pemasangan: 92mm x 92mm
D: 72mm x 72mm x 110mm lubang pemasangan: 68mm x 68mm
E: 48mm x 96mm x 110mm lubang pemasangan: 44mm x 92mm
F: 96mm x 48mm x 110mm lubang pemasangan: 92mm x 44mm
S: 80mm x 160mm x 120mm lubang pemasangan: 76mm x 156mm
G: 48mm x 48mm x 110mm lubang pemasangan: 44mm x 44mm
(2) Reka bentuk nombor siri
(3) penggera
"0": tiada penggera "1or2": satu penggera (had atas, had bawah) "5": Penggera suara
"3": Penggera Dua Kumpulan (had atas, had bawah, penggera sisihan positif dan sisihan negatif penggera sisihan sisihan)
(4) isyarat input
"8": Pertukaran percuma isyarat input
Kaedah Kontrol
Kosong: Hubungi Relay
"A": Penyesuaian pencetus over-sifar tunggal fasa
"A3": Pelarasan pencetus lebih-sifar tiga fasa
"B": Pelarasan pencetus fasa fasa tunggal
"B3": Pelarasan pencetus fasa tiga fasa
"C": 0-10mA atau 4-20mA output semasa elektrik berterusan
"G": Output Relay Negeri Pepejal (SSR)
Ⅲ 、 Arahan panel (berunding)
Ⅳ 、 mod tetapan kod
Series |
Code |
Name |
Setting range |
Manual |
Remarks |
0 |
SP |
Appointed data |
Determined by P-SL P-SH |
- |
50.0 |
1 |
AL-1 |
Alarm 1 |
Determined by P-SL,P-SH when the upper and lower limit range,it is0~50.0 when the upper and lower limit deviation alarm |
Alarm 1 setting value |
10 |
2 |
AL-2 |
Alarm 2 |
Determined by P-SL,P-SH when the upper and lower limit range,it is0~50.0 when the upper and lower limit deviation alarm |
Alarm 1 setting value |
10 |
3 |
P |
Proportion modulus |
0~100 |
When the P↑,the the proportion function↓ When P=0,the meter is ON/OFF control |
8 |
4 |
I |
Calculus time |
0~2000S |
240 |
|
5 |
d |
differential time |
0~200S |
30 |
|
6 |
At |
Setting itself |
ON:open setting inself function OFF:close setting itself function |
Select of setting itself |
OFF |
7 |
t |
SSR proportion Control period |
1~120S |
the movements cycle ON/OFF of Setting relays control is no meaning |
20 |
8 |
Hy |
Main control by drop in level |
0.1~50.0 |
Only have meaning when main control output is ON/OFF(P=0) |
1.0 |
9 |
Hy-1 |
Alarm 1 drop in level |
0.1~50.0 |
It has use drop in level setting of alarm contact output |
1.0 |
10 |
Hy-2 |
Alarm 2 drop in level |
0.1~50.0 |
It has use dropin level setting of alarm contact output |
1.0 |
11 |
Pb |
Sensor error amendment |
±20.0 |
The sensor have deviation can use item to revisal |
0 |
12 |
FILT |
Filt modulus |
0~50 |
Is the software filter constants of measurement sampling.The constant ↑,the Measurements antijamming capabilityMeasurements antijamming capability↑,but the measurement and system time ↓ |
20 |
13 |
dp |
Show accuracy |
0~1 |
0: have radix point,1: have no radix point |
- |
14 |
P-SH |
Display the high limit |
P-SL~9999 |
Can set the high limit displaying input signal |
400 |
15 |
P-SL |
Display the low limit |
-1999~P-SH |
Can set the low limit displaying input signal |
0 |
16 |
OUTL |
Allow exports min value |
0~OUTH |
It will no role when highest outputlimit,,manual and position. |
200.0 |
17 |
OUTH |
Allow exports max value |
OUTL~200 |
It will no role when lowest outputlimit,,manual and position. |
0.0 |
18 |
ALP1 |
Alarm1 and output definition |
0~4 |
‘0’:indicate no alarm
‘1’:upper limit touch alarm ‘2’:lower limit touch alarm ‘3’:upper windage alarm ‘4’:lower windage alarm |
- |
19 |
ALP2 |
Alarm2 and output definition |
0~4 |
- |
|
20 |
COOL |
System function choice |
0~1 |
‘0’:reverse control ‘1’:positive control |
0 |
21 |
OPPO |
Open power output |
0~100 |
Soft start functionthat meters coefficient after first export of electric power |
0 |
22 |
LOCK |
Code lock |
0~50 |
0- all the parameter can be revised 1- only the sp can be revised |
0 |
23 |
Sn |
Input type |
0~70. |
0-CU50 (-50.0~150.0℃) ;1-PT1 (-200.0~200.0℃) ;2-PT2 (-200.0~600.0℃) ;3-K (0~1300℃) ;4-E (0~700.0℃) ;5-J (0~900.0℃) ;6-T (-200~400.0℃) ;7-S (0~1600℃) ; | |
24 |
OP-A |
Output type |
1~4 |
1- RLP SSR output mode 2- SSR solid state relay 3- Zero controllable silicon contact signal when it exceed zero output mode 4- Mut controllable silicon phase trigger contact output mode 5- 0~10MA linearity control electric current output 6- 4~20MA linearity control electric current output |
Ⅴ 、 indeks teknikal
1 、 kawasan penetapan pertama
Tekan kekunci set 3s masuk ke kawasan tetapan pertama, meter akan memaparkan kod parameter 1 ~ 24in tetingkap di baris atas dan paparkan data parameter pada baris rendah. Pada masa ini tekan kekunci ▲ 、 ▼ atau T untuk menyesuaikan parameter, kemudian tekan kekunci set untuk dipelihara. Tekan kekunci set lama akan menarik balik atau tekan kekunci set + ƒ akan secara langsung menarik diri. Jika dalam masa 10 saat tidak tekan setiap kekunci maka ia akan secara automatik untuk memelihara data dan menarik balik tetapan.
2 、 kawasan tetapan kedua
Apabila meter disediakan dengan elektrik, tekan kekunci set masuk ke kawasan tetapan kedua, anda boleh mengikut 1 untuk menetapkan "SP".
3 、 Peraturan Manual
Apabila meter ditubuhkan dengan elektrik, tekan kekunci T kira -kira 3s masuk ke dalam peraturan manual, ia akan memaparkan "H" pada baris bawah, pada masa ini boleh menetapkan kuasa output; Tekan kekunci T tentang 3s sekali lagi ia akan menarik balik peraturan manual.
Ⅵ 、 Menetapkan sendiri
Penggunaan meter pada kali pertama atau persekitaran mempunyai penukar, mendapati ia tidak baik, pada masa ini anda perlu menggunakan tetapan itu sendiri. Sebagai contoh:
Yang pertama menetapkan at = pada, cahaya saya berkedip, meter masuk ke dalam tetapan itu sendiri, tekan kekunci set masuk ke dalam tetapan parameter. Tetapkan HY ialah 0.5 ~ 1 ℃, jika output adalah relay set t = 2s, meter mempunyai tiga kali bergetar, parameter p, i, d yang dipelihara secara automatik dan cahaya, tetapan itu sendiri selesai.
Skim Sambungan ⅶ 、 (berunding)